LED Lighting Implementation as a Strategy for Energy Saving in Energetically Sustainable Campus

LED Lighting Implementation as a Strategy for Energy Saving in Energetically Sustainable Campus

Volume 4, Issue 5, Page No 360-368, 2019

Author’s Name: Pablo Pérez-Gosende1,2,a)

View Affiliations

1Grupo de Investigación Interdisciplinar en Matemática Aplicada (GIIMA), Universidad Politécnica Salesiana, 090109, Ecuador
2Centro de Investigación en Gestión e Ingeniería de Producción (CIGIP), Universitat Politècnica de València, Alcoy, 03801, Spain

a)Author to whom correspondence should be addressed. E-mail: pperezg@ups.edu.ec

Adv. Sci. Technol. Eng. Syst. J. 4(5), 360-368 (2019); a  DOI: 10.25046/aj040547

Keywords: AHP, Dialux, Energy-saving strategy, LED lighting

Share
751 Downloads

Export Citations

Since lighting constitutes an important part of the total electricity consumption of a country, the design and implementation of more efficient interior lighting systems are one of the feasible strategies to reduce energy consumption. With this purpose, in recent years several studies have considered the use of LED lighting systems. However, its implementation at a large scale is still unaffordable for some organizations like academic institutions. In this context, this research presents a strategy to replace the current fluorescent-based lighting system to LED technology in a building of a higher education institution in Ecuador, and thus contribute to reducing energy consumption in campus facilities. The appropriate LED lamp alternative was selected from those available in the Ecuadorian market through AHP multicriteria decision-making method. The improvement proposal included an annual schedule for the progressive replacement of fluorescent lamps, based on the economic savings that would be generated every year after its implementation. The proposal was technically validated by simulation in DIAlux 4.12 and its economic feasibility was demonstrated by estimating the net present value and the equivalent uniform annual cost. With this strategy, a total of 2595 fluorescent tubes installed in the 215 building light points, can be replaced with LED technology in three years, with an initial investment of 4949.10 USD and generate an energy saving of 47.36%.

Received: 04 August 2019, Accepted: 13 September 2019, Published Online: 22 October 2019

1. Introduction

Given the high level of pollution generated in the environment by the production of electricity based on fossil fuels, it is evident that there is a need to draw up strategies to reduce energy consumption. For this purpose, one of the feasible strategies consists in the design and implementation of more efficient interior lighting systems [1], since lighting constitutes an important part of a country’s total electricity consumption [2]. It has been reported that in industrialized countries, lighting represents 20% of the total energy consumption [3].

The optimization of indoor lighting systems is a matter of great interest to the scientific community [4]. Approximately 21% of all the electricity produced in the world is consumed in lighting [5]. Some more specific studies show that the electric energy consumed by lighting systems represents 50% of the total energy consumption in office buildings, between 20% and 30% in hospitals, 15% in manufacturing factories and from 10 to 15 % in schools [4,6].

In the USA approximately 31% of all electrical consumption in academic buildings is due to lighting systems [7]. In Europe, this value is approximately 50% [8]. The reduction of energy consumption through the design and implementation of more efficient lighting systems is an important solution to the problem [5], but not the only one. Other possible ways to reduce the energy consumption related to lighting in buildings include the creation of awareness in the users, the adjustment or organization of the furniture and other elements within the space in a way that allows to take advantage of the natural light that enters through the windows, or the installation of motion sensors and control systems that modulate the intensity of the light according to the needs or turn it off when the space is not being occupied.

In recent years, several studies have considered the implementation of LED lighting (Light-Emitting Diodes) to reduce the electricity consumption of the facilities and thus contribute to the energy efficiency in buildings [1,4,5,9,10]. LED lighting has gained special relevance in recent years over traditional lighting technologies due to its high efficiency, long lifespan and low maintenance cost. However, its impact on energy savings in industrialized countries has been questioned [3].

LEDs can produce high luminous fluxes with low heat emission and maintain their light output efficiency for years. Incandescent (IL) and fluorescent (FL) bulbs contain filaments that must be replaced periodically and consume a lot of electrical energy while generating heat [11]. The duration of the fluorescent bulbs is of the order of 20,000 hours, while the incandescent bulbs last approximately 1000 hours. LEDs, on the other hand, do not have filaments, and therefore, they do not burn like incandescent or fluorescent bulbs. Normally, commercial LED lamps have a lifespan of 30,000 to 50,000 hours.

The design of an interior lighting system should consider, in addition to energy efficiency, the visual performance and comfort of users [5]. Particularly in educational institutions, the implemented lighting systems should provide a pleasant and stimulating environment that allows students, teachers and administrative staff in general, to perform their activities without excessive visual effort, avoiding fatigue, headaches and the prevalence of vision disorders provoked by inadequate lighting [12]. For this reason, the lighting system in educational institutions should be monitored with a certain frequency to guarantee the correct development of the teaching-learning processes.

In Ecuador, the 2393 Executive Decree that regulates the levels of lighting is not very demanding, or at least not very precise in terms of the levels of lighting suitable for each activity [13]. On the other hand, public or private institutions are not required to carry out light audits to detect deficiencies in lighting systems. Therefore, it is extremely important to give concrete answers to the reduction of energy consumption in Higher Education Institutions (HEIs) by searching for more efficient lighting alternatives without neglecting compliance with current regulations regarding health and safety.

In this context, this study proposes an energy-saving strategy based on the progressive implementation of LED lighting in an academic building of an HEI located in the city of Guayaquil.

This research is part of a wider scope project named “Sustainable Energy Campus Model” developed by the Interdisciplinary Research Group in Applied Mathematics (GIIMA) of the Universidad Politécnica Salesiana in conjunction with the Interdisciplinary Modeling Group (InterTech) of the Universitat Politècnica de València. The results of the project will allow, in the medium term, to optimize the energy consumption for lighting, air conditioning and the use of computers in the institution. The future savings generated by the improvements proposals within this project could further strengthen the university infrastructure, especially in the setting and equipment of new laboratories and the increase and updating of the literary heritage available in the university library.

2. Methods

The research is quantitative with a descriptive approach. The HEI under study is located in the city of Guayaquil, Ecuador, and is composed of six buildings. These, in turn, are composed mostly of classrooms, laboratories, teacher workrooms, administrative offices, auditoriums, hallways, bathrooms, and storage areas.

Illuminance measurements were taken in the facilities of one of these buildings between October 2017 and February 2018 by four AMPROBE lux meters model LM100, with an accuracy of ± 5% + 5 digits. The dimensions of the facilities, as well as the distance from the work surface to the light points, were obtained through a Capital laser distance meter, model CP-3007, with an accuracy of ± 0.5% and resolution of 0.01m.

The replacement strategy of the current lighting system based on FL to LED technology, included an annual schedule for the progressive replacement of fluorescent lamps, based on the economic savings that would be generated every year after its implementation. For this, the LED lamp alternative suitable for the building’s facilities was selected from those available in the Ecuadorian market using the AHP multicriteria method [14].

For the improvement proposal technical validation, it was used DIALux 4.12 software. Facilities were modeled and the lighting levels that would be obtained once the lamps were installed were simulated. In this regard, it was possible to verify in each case the fulfillment of the minimum illuminance requirements established in the national and international regulations used as a reference in this work [12,13].

For the economic validation of the improvement proposal, using (1), the net present value (NPV) of the costs was calculated and compared for the two project alternatives: (A) The progressive replacement to LED lighting or (B) to keep the current FL-based lighting system.

By progressively replacing the current FL-based lighting system with LED technology, energy consumption will decrease and this will generate economic savings. This saving has been taken into account in this investigation for the determination of the annual present value (PVj), considering as such the updated value of the difference between the total costs (TCj) and the future annual benefits (ESj) as presented in (2).

Likewise, the economic analysis included the equivalent annual uniform cost estimation (EAUC) for each alternative throughout its expected time horizon. EAUC consists of converting all expenditures into a uniform series of payments [15] and is frequently used in the evaluation of investment projects where revenues are not relevant, but costs. It is formulated as in (3) and its value depends on the capital cost or discount rate (i) and the NPV of the amounts of cash outflows from year j=0 to year j=n. When comparing several alternatives of mutually exclusive projects, the one with minor EAUC should be selected [15,16].

The relevant benefits and costs items for NPV calculation (expressed in $/year) are obtained from the following equations. There, AC represents the annual cost of lamps acquisition, EC the annual electricity consumption cost, DC the cost of the final disposal of the fluorescent lamps that are replaced and ES corresponds to the annual economic benefit that represents the energy savings by the use of LED lamps instead of FL. In addition, L represents the quantity of lamps expressed in units (u), Pr the wholesale price of the lamp ($/u), P the power of the lamp (W), H the estimated daily use time of the lamp, D the number of days per year in which the institution operates and T is the electric rate ($/kWh). Also, WFL refers to the average weight of a 60cm long fluorescent lamp (Kg/u) and PrD means the price of the specialized recycling service for the final disposal of FL ($/Kg).

3. Results

In this section it is reported the results of the light audit, the selection of the most suitable LED lamp alternative for educational facilities according to certain relevant factors, the proposed replacement schedule and the technical and economic validation of the improvement proposal.

3.1.  Indoor lighting audit

The building under study is one of the six that comprise the campus. There were identified 50 classrooms, 4 hallways, 18 restrooms, 8 computer laboratories, 4 teacher  workrooms, 5 administrative offices, a medical department, a supply warehouse, a restaurant/coffee shop and a copy center, all of them illuminated by 60 cm long linear fluorescent lamps with powers of 17, 18 and 32W. 215 light points and 2595 fluorescent tubes were counted throughout the building. The chapel, the theater, and the auditoriums do operate with compact fluorescent lamps (CFL) downlight style.

In the building, several careers carry out their daily academic activities in three sessions: morning (07h00-13h00), evening (14h00-18h00) and night (18h00-22h15). The existence of a night session facilitates the students to work and attend University at the same time and is one of the differentiating elements of this HEI in the city. After the last shift of classes, it takes an hour for the cleaning team to organize all the classrooms for the next day.

According to the above, in this study, it has been considered that the lighting system remains on 16 hours a day, 288 days a year. The illuminance measurements were made at night, between 7:00 p.m. and 10:00 p.m. In each location, illuminance measurements were taken at the height of the work surface (0.77m in classrooms and 0.8m in laboratories) at five different points, and the average value was taken as a reference.

The legislation that regulates indoor and outdoor lighting levels in Ecuador is the 2393 Executive Decree: Regulation of safety and health of workers and improvement of the work environment [13], however, this norm does not establish specific illuminance values ​​for academic activities given its generality. From its content, it is assumed that the reading and writing activities that take place in a classroom, as well as those that take place in a computer laboratory,  can be done with a minimum lighting level of 300 lx since in these cases the average distinction of details is essential. In these facilities would not be justified an illuminance of 500 lx, which is the value established in the standard for works in which a fine distinction of details under conditions of contrast is indispensable.

Given the lack of specificity in the Ecuadorian regulations, this research also took as a reference to the European standard on indoor lighting EN 12464.1, which includes minimum illuminance values ​​for educational establishments [12]. Table 1 shows a comparison of the levels of illumination allowed for the facilities at the academic building under study in this investigation according to both regulations. In case of disparity, the highest minimum permissible illuminance value was taken as reference.

According to the above, it was identified that 98% of the building facilities do not comply with the lighting requirements established in the national regulation and the European standard for indoor lighting. Note also that only the chapel and the restaurant/coffee shop meet the reference standard used in this investigation.

The noncompliance with the lighting levels required for the facilities was corroborated through its simulation in DIAlux 4.12. Taking as an example a standard classroom model of 6.80m x 6.70m x 3.25m, considering a maintenance factor of 0.8, a height of the work plane of 0.77m, six light points and three FL lamps of 17W in every light point, the resulting illuminance isoline diagram (Figure 1) shows illuminance values below the 300 lx requirement established in regulations for this type of facility.

Figure 1: Illuminance isoline diagram for a standard model classroom

3.2.  LED lamps selection

To verify more economical lighting alternatives and contribute to the campus energy saving, it was decided to implement LED lighting, as this technology is more efficient, generates less consumption given its low power, in addition to its longer lifespan.

Unified Glare Index, UGR), efficiency (lm/W) and light type. Then, as all the identified alternatives provided light in a neutral white tone and had a UGR<19, the criteria type light and glare were discarded from the final decision process.

The decision criteria that were taken into account for LED lamp selection were: power (W), lifespan (h), wholesale price (USD), color rendering index (CRI), glare (measured by the

Table 1: Compliance with illuminance reference standards for academic buildings

Facilities Standard Reference standard Total of  facilities Facilities that do not meet the standard Measured illuminance Illuminance needed to meet the standard

Decree

No. 2393

EN 12464.1 μ σ μ σ
Classrooms 300 lx 300 lx 300 lx 50 50 130 46.30 170 46.30
Hallways 20 lx 100 lx 100 lx 4 4 54 12.53 47 12.53
Restrooms 50 lx 200 lx 200 lx 18 18 35 8.03 165 8.03
Computer laboratories 300 lx 300 lx 300 lx 8 8 139 36.60 161 36.60
Teacher workrooms Not specified 300 lx 300 lx 4 4 112 38.24 189 38.24
Administrative offices 300 lx 300 lx 300 lx 5 5 113 33.68 187 33.68
Medical department Not specified 500 lx 500 lx 1 1 225 0 275 0
Warehouse 200 lx 100 lx 200 lx 1 1 140 0 60 0
Restaurant and coffee shop Not specified a Not specified 100 lx 1 0 260 0 0 0
Chapel Not specified Not specified 100 lx 1 0 178 0 0 0
Copy center 300 lx 300 lx 300 lx 1 1 145 0 355 0
Theater Not specified Not specified 100 lx 1 1 84 0 16 0
Auditoriums Not specified 500 lx 500 lx 2 2 169 43 331 43

a For this case, the European standard states as appropriate any value of illuminance that allows creating an appropriate atmosphere. Source: Own elaboration based on the requirements in the national and European standards referred to in [12, 13].

 

The hierarchical decision model followed in this research for the selection of the LED lamp by the Saaty Analytical Hierarchic Process (AHP) is shown in Figure 2. In the scheme, the zero level represents the decision objective, the level one the decision criteria considered, and level two presents a selection of the few alternatives of linear 60cm long LED lamps available in the Ecuadorian market that could be installed in the bases of existing fluorescent luminaires. This last consideration was necessary to reduce the cost of the replacement process, since LED luminaires, despite their benefits, currently continue to be more expensive than FL.

The comparison of the importance or preference between each pair of criteria using the Saaty scale [14], led to a reciprocal matrix (R) so that rij represents the relative priority between criterion Ci and criterion Cj with respect to the objective or goal of the problem.

The results of the normalization of the paired comparisons are presented in the RNORM matrix and the resulting priority vector in the W matrix.

The process of paired comparisons of the criteria yielded a consistency index of 9.08%, so it is considered that the matrix R has an admissible consistency and the vector of priorities obtained (W) is accepted as valid.

As could be interpreted in Figure 2, all the decision criteria are quantitative variables, so it would not be relevant to make comparisons between alternatives concerning each variable using the subjective scale of Saaty. Consequently, with the values identified for each decision variable in each alternative, the M matrix was generated. Here, every mij represents the value that the lamp alternative i takes in variable j.

Figure 2: Hierarchical decision model for LED lamp selection

Note that the above mentioned power and wholesale price criteria are to be minimized, while lifespan, color performance, and efficiency are to be maximized. Thus, it was necessary to homogenize the M matrix to the MNORM matrix. The latter is composed of all the local priority vectors of the alternatives for each criterion.

Then, the global priority vector of the alternatives was obtained from the multiplication of the alternative priority vectors concerning the decision criteria (MNORM matrix) with the priority vector of the criteria with respect to the objective (W matrix).

From here it is concluded that the most suitable LED lamp alternative according to the previously defined decision criteria is the Americanlite AL572518. This LED tube, measuring 60cm in length, emits neutral white light, has a power of 9W, 40000h of lifespan, wholesale price of $ 3.90, IRC equal to 80, UGR<19 and average efficiency of 130 lm/W.

3.3.  Technical validation of the selected lamp

Taking into account the selected lamp model, the facilities were modeled and the lighting system was simulated using the DIAlux 4.12 software.

Taking the simulation of a standard classroom as an example and considering three LED tubes in each of the six pre-existing light points, the resulting illuminance isoline diagram shows values equal to or greater than those established in the regulations for this type of facility (300 lx) in most of the useful area of the classroom (Figure 3). More specifically, the Dialux report showed an average illuminance value on the work plane of 326 lx, 204 lx on the floor, 70 lx on the ceiling and 52 lx on the walls.

On the other hand, the resulting color performance diagram is shown in Figure 4. The red color on the work surfaces ensures that if the selected LED lamp is implemented, without having to increase the number of light points, it is possible to guarantee the minimum illuminance requirements established in the regulations. This validates from the technical point of view the suitability of the selected lamp for the building’s facilities, which are mostly classrooms with similar characteristics.

Figure 3: Illuminance isoline diagram for a standard model classroom

Figure 4: False color rendering

3.4.  Replacement strategy

Given the high cost that comprises to shift all the fluorescent lamps at once, it is recommended the replacement to be gradual, prioritizing those facilities with greater gaps to meet the lighting standards.  For the building under interest in this research, it is proposed to follow the lamp replacement schedule represented in Table 2 with their respective prioritization criteria. As may be seen, the classrooms and computer laboratories were prioritized, since within these facilities are commonly developed the academic activities that are the central axis of the University formative mission.

Table 2: Schedule for replacement of FL by LED lamps

Priority level Facility Quantity a Priority criteria Required lamps Schedule
1 Classrooms 15 (RS – IM) ≥ 200 lx 405 First year
2 Computer Laboratories 7 (RS – IM) ≥ 100 lx 189
3 Classrooms 25 150 ≤ (RS–IM) < 200 lx 297 Second year
4 Computer laboratories 1 (RS – IM) < 100 lx 27
5 Classrooms 10 (RS – IM) < 150 lx 270
6 Medical department 1 12
7 Teacher workrooms 4 144
8 Administrative offices 5 135
9 Auditoriums 2 78
10 Hallways 4 324
11 Warehouse 1 3
12 Copy center 1 18
13 Theater 1 49
14 Restaurant and coffee shop 1 12
15 Chapel 1 38 Third year
16 Restrooms 18 216

a RS represents the value of the reference illuminance standard according to regulations. IM refers to the actual average illuminance measured in the facilities. In areas where no prioritization criteria were applied, all lamps will be replaced at the same time.

 

It is worth noting that as part of the replacement strategy and after the first year of the initial investment, it has been considered that the new lamps to be installed are to be obtained with the amount equivalent to the economic value saved by the institution the previous year due to the use of LED technology instead of fluorescent technology.

3.5.  Economic validation of the improvement proposal

For the economic validation of the improvement proposal, two alternative strategies were considered: (A) To implement the progressive replacement to LED lighting proposed in this study or (B) To continue with the current FL-based lighting system. The energy consumption and annual economic expenditure estimated in each case are referred to in Table 3.

From the above, it is assumed that the current FL-based lighting system electricity costs represent on average 10.93% of the total electrical energy consumed in the building (95% CI: 9.89-11.98), taking into account that during the last 18 months of operation, the total average cost of the building was $ 13,657.94 (95% CI: 12434.50-14881.38).

The investment cycle for strategy (A) and (B), has an estimated time horizon of eight and two years, respectively, considering the average lifespan of the corresponding lamp, the 16 hours of daily use and the 288 days of annual operation of the institution. Then, since both alternatives are mutually exclusive and have different lifetimes, the comparison of their net present values ​​must be made on the least common multiple of years, in this case, 8 years. According to this, Table 4 shows all possible expenditures and benefits for each alternative. In it, for the calculation of the present values ​​of the annual differences between costs and benefits, the active interest rate of 7.26% established by the Central Bank of Ecuador for March 2018 [17] was considered as the minimum attractive rate of return (MARR).

It is important to clarify that in the estimation of the total costs there have not been considered salary expenses of the personnel that will perform the replacement of the fluorescent lamps for those with LED technology, given that the University has maintenance personnel hired and their salaries are debited from the annual operations budget.

With the data in Table 4, a NPV of $56115.02 was calculated for alternative 1, while for alternative 2 the resulting NPV was $133188.18. Then, with the updated values of the differences between costs and benefits, the EUAC was estimated for each alternative considering their respective life cycles. In this regard, the strategy of the progressive switch to LED lighting yielded a EUAC equal to $8868.28, while the alternative of doing nothing and maintain the current FL lighting system was $20669.26. This result shows that the alternative based on LED technology has lower NPV and lower EUAC, which means it is the most feasible alternative from the economic point of view.

Finally, the graph in Figure 5 shows the trend of total costs for both alternatives over time, in addition to the behavior of economic savings and the acquisition cost of LED lamps.

Figure 5: Some relevant cost functions

As can be seen in Figure 5, the strategy of progressive replacement to LED lighting (Strategy a) is less costly during the replacement period (three years) and during the rest of the investment’s life cycle. In the same way, it is observed that once the total conversion of the system has been made, the economic saving for the use of LED lighting (with respect to the current system based on FL) would cover the acquisition costs of the new luminaires that are needed at the end of the investment life, guaranteeing the sustainability in time of the proposed system.

Table 3: Energy consumption and annual electricity expenditure for lighting systems based on FL and LED

Facilities Quantity Total of lamps FL Lighting system LED Lighting system
Power consumed (kW) Power consumption (kWh/year) Energy cost ($/year) Power consumed (kW) Power consumption (kWh/year) Energy cost ($/year)
Classrooms 50 1350 22.95 105753.60 9517.82 12.15 55987.20 5038.85
Hallways 4 324 5.508 25380.86 2284.28 2.916 13436.93 1209.32
Restrooms 18 216 3.672 16920.58 1522.85 1.944 8957.95 806.22
Computer laboratories 8 216 3.672 16920.58 1522.85 1.944 8957.95 806.22
Teacher workrooms 4 144 2.448 11280.38 1015.23 1.296 5971.97 537.48
Administrative offices 5 135 2.295 10575.36 951.78 1.215 5598.72 503.88
Medical department 1 12 0.216 995.33 89.58 0.108 497.66 44.79
Warehouse 1 3 0.054 248.83 22.39 0.027 124.42 11.20
Restaurant and coffee shop 1 12 0.384 1769.47 159.25 0.108 497.66 44.79
Chapel 1 38 0.684 3151.87 283.67 0.342 1575.94 141.83
Copy center 1 18 0.306 1410.05 126.90 0.162 746.50 67.18
aTheater 1 49 0.882 31.75 2.86 0.441 15.88 1.43
aAuditoriums 2 78 1.404 808.70 72.78 0.702 404.35 36.39
Total 97 2595 22.95 195247.37 17572.26 23.36 102773.12 9249.58

a In the case of the auditoriums, an average use of 2h per day was considered, and for the theater 8h per month, wich is equivalent to 0.3h per day.

 

4. Discussion

This research shows that the progressive implementation of LED lighting in an academic building is a strategy that can contribute substantially to the energy and economic savings of a Higher Education Institution.

A lighting audit found that 98% of the building’s facilities do not meet the illuminance requirements included in national and international regulations [12,13]. Likewise, it was detected that the energy consumption of the current FL-based lighting system represents 10.93% of the total electric energy consumed in the building, a value considered high, despite being located within the range of 10 to 15% identified by other similar studies in educational institutions [4,6].

These reasons justify the need to implement a strategy to optimize energy saving through lighting system in the building, which at the same time, favors the performance and visual comfort of users through compliance with current regulations on occupational health and safety.

In response to this need, this research presents a strategy for the progressive replacement of the current FL-based lighting system to LED lighting, with a duration of three years, which guarantees compliance with the minimum levels of lighting required by national and international regulations for each facility and allows to obtain an energy saving of 47.36%. This value would represent an economic saving of $8322.68 per year for the institution and would allow the total coverage of the new luminaires that are needed at the end of the investment lifecycle.

Since the instantaneous conversion to LED lighting can be unfeasible from the economic point of view due to the high amount of the initial investment, the strategy suggested in this research prioritizes the replacement in those facilities with a greater need for illuminance to meet the requirements on national and European regulations. In this concern, the planned replacement of lamps can be covered with the amount equivalent to the economic value saved by the institution the previous year due to the use of LED technology instead of FL technology. Another element of importance to highlight in order to reduce installation costs was the consideration of the same number of pre-existing light points.

According to the above, the amount of the initial investment of $4949.10 will allow replacing 48.90% of the lighting system. Then, with the energy savings of the first year, 1072 LED lamps could be acquired to increase coverage to 90.21%. Finally, with the energy savings of the second year, the remaining 254 lamps can be acquired to cover 100% of the building’s needs according to the planned schedule.

The technical validity of the improvement proposal was obtained by modeling and simulating all the building’s facilities in the free software DIALux, which is one of the most commonly used tools in lighting systems simulation [1,4,5,9,10,18–21]. In this regard, this research demonstrates that the results of the simulation in DIALux are very similar to those on-site

Table 4. Costs and benefits of the alternatives: (a) Progressive change to LED lighting and (b) Current lighting system based on FL

Alternatives a Cost ítems Year 1 Year 2 Year 3 Year 4 Year 5 Year 6 Year 7 Year 8

(A)

Progressive swift to LED lighting

a 4949.10 4180.80 990.60 0 0 0 0 0
b 4736.52 8482.99 14167.56 14167.56 14167.56 14167.56 14167.56 14167.56
c 7465.58 1806.52 0 0 0 0 0 0
d 390.85 330.18 78.23 0 0 0 0 0
e 17542.05 14800.49 15236.39 14167.56 14167.56 14167.56 14167.56 14167.56
f 4210.24 3690.18 858.47 8504.14 8504.14 8504.14 8504.14 8504.14
g 12429.44 9657.19 11651.52 4278.85 3989.23 3719.22 3467.48 3232.78

(B)

Maintain the current FL-based lighting system

a 2334.60 2334.60 2334.60 2334.60 2334.60 2334.60 2334.60 2334.60
c 17935.19 17935.19 17935.19 17935.19 17935.19 17935.19 17935.19 17935.19
d 399.48 399.48 399.48 399.48 399.48 399.48 399.48 399.48
e 20669.26 20669.26 20669.26 20669.26 20669.26 20669.26 20669.26 20669.26
g 19270.24 17965.92 16749.88 15616.15 14559.15 13573.70 12654.95 11798.39

a The cost items considered are: a) Acquisition, b) Annual energy consumption in LED lighting, c) Annual energy consumption in FL lighting d) Cost of the final disposal of FL, e) Total cost, f) Economic saving by the use of LED versus FL and g) Present value of the difference between costs and benefits.

 

measurements, confirming what was reported in previous studies [10,21].

Several authors have proposed the adoption of LED lighting as an alternative to the reduction of energy consumption in educational facilities [1,4,5,18,21]. However, these studies start from the use of a specific luminaire model, devaluing the analysis of other alternatives through a multicriteria decision method. In this research, the application of the AHP method for this purpose demonstrated feasibility and relevance. In the same way, the lamps selection criteria here used and their respective levels of relative importance may constitute a starting point for future research to strengthen lamp selection decisions.

Another important element to highlight is that the studies that have validated the implementation of indoor LED lighting systems as the best strategy against traditional lighting technologies [1,4,5,9,18], do not consider the costs of the final disposal of a massive FL replacement. Fluorescent and compact fluorescent lamps contain Mercury, a potentially dangerous element for the environment, so the final disposal of these lamps must be handled carefully through special recycling techniques [2,3]. For this reason, in this research when estimating the costs for each alternative, in addition to the acquisition costs and the annual energy consumption, the cost of the final disposal of the replaced FL was included.

In the economic analysis of alternative lighting systems for interiors, it is common to calculate the Simple Payback Period (SPBP) or the whole lifecycle cost (WLC) without considering the value of money in the time [1,4,10,19], although some authors consider that these techniques should not be used as the primary measure of value to select a project alternative [15,16]. The consideration of the net present value (NPV) or the equivalent annual uniform cost (EAUC) as economic evaluation tools is not common in the literature.

In this context, the strategy of progressive change to LED lighting proposed in this research yielded a VPN of $ 56115.02. This means that if the institution had to disburse today the amount required to cover the lighting costs of the next eight years, it would be more economical to have a lighting system based on LED technology since maintaining the current FL-based system would be 42% more expensive. Likewise, for the first strategy, the estimated EAUC was $ 8868.28, less than the value of $ 20669.26 which would represent maintaining the current system based on FL technology. This allows validating that the first alternative is more feasible from the economic point of view, and at the same time confirms the relevance of the VPN and the EAUC as economic evaluation tools for mutually exclusive investment project alternatives with different life cycles where generally only the costs are relevant.

Finally, the authors would like to point out that the reduction of energy consumption in a university campus, not only depends on the implementation of strategies such as the adoption of a more efficient and safe lighting system like the one suggested in this work. Energy-saving must be a shared social responsibility of all those who make the University a common resource for the entire Society. In this regard, HEIs should take advantage of their transformative capacity to raise awareness among their students, teachers and administrative staff about the need to contribute to energy savings and thereby maximize the contribution that is made from the academy towards environmental sustainability.

5. Conclusions

This work showed that despite the high cost of LED lighting, it is feasible from a technical and economic point of view to converting an FL lighting system set in educational institutions through the implementation of a progressive replacement strategy. The suggested strategy guarantees the total replacement of the current lighting system of a university building consisting of 215 light points and 2595 FL, in three years, with an initial investment of 4949.10 USD, generating an energy saving of 47.36%.

Through simulation in DIALux 4.12, it was demonstrated that the proposed LED lighting system will cover the minimum indoor lighting levels established in national and international regulations for educational facilities. The estimation of the investment net present value, as well as its equivalent annual uniform cost, proved the economic feasibility of the improvement proposal.

The results of this work could constitute a reference for the administrative management of public universities in developing countries, which increasingly receive fewer resources from governments. The economic savings for the implementation of more efficient lighting systems could contribute to the strengthening of university infrastructure and the offering of better educational services. At the same time, the energy savings generated would have a positive impact on the reduction of the emission of greenhouse gases into the atmosphere. In this regard, future research should pay more attention to the combination of more efficient lighting systems with cleaner energy sources, to maximize the contribution that is made from the academy to the sustainability of the environment.

Conflict of Interest

The authors declare no conflict of interest.

Acknowledgment

Authors would like to thank Universidad Politécnica Salesiana for funding this research under the resolution No. 03-006-2017-05-30 of Guayaquil Campus Research Council. Also, a special acknowledge is dedicated to all the industrial engineering students who helped to collect relevant data for the lighting audit in all the facilities of the academic building.

  1.  N. Tshikuvhe, M. Nthontho, S. P. Chowdhury, S. Chowdhury, “Cost effective carbon mitigation through energy efficiency: A case for a university student residence lighting in Cape Town,” in 2013 IEEE African Conference (Africon), Pointe-Aux-Piments, Mauritius, 2013. https://doi.org/ 10.1109/AFRCON.2013.6757686
  2.  M. M. Aman, G. B. Jasmon, H. Mokhlis, A. H. A. Bakar, “Analysis of the performance of domestic lighting lamps,” Energ. Policy, 52, 482–500, 2013. https://doi.org/ 10.1016/j.enpol.2012.09.068
  3.  B. Gayral, “LEDs for lighting: Basic physics and prospects for energy savings,” Comptes Rendus Phys., vol. 18, no. 7–8, pp. 453–461, Sep. 2017. https://doi.org/10.1016/j.crhy.2017.09.001
  4. F. Salata, I. Golasi, M. di Salvatore, and A. de Lieto Vollaro, “Energy and reliability optimization of a system that combines daylighting and artificial sources. A case study carried out in academic buildings,” Appl. Energ, 169, 250–266, 2016. https://doi.org/10.1016/j.apenergy.2016.02.022
  5. P. Sathya, R. Natarajan, “Energy estimation and photometric measurements of LED lighting in laboratory,” in 2014 International Conference on Advances in Electrical Engineering (ICAEE), Tamilnadu, India, 2014. https://doi.org/10.1109/ICAEE.2014.6838470
  6. B. Atanasiu, C. Despret, M. Economidou, J. Maio, I. Nolte, O. Rapf, “Europe’s Buildings under the Microscope: A Country-by-Country Review of the Energy Performance of Buildings,” Build. Perform. Inst. Eur., 2011.
  7. J. Min, I. L. Azevedo, P. Hakkarainen, “Assessing regional differences in lighting heat replacement effects in residential buildings across the United States,” Appl. Energy, 141, 12–18, 2015. https://doi.org/10.1016/ J.APENERGY.2014.11.031
  8. Y. Nikolaidis, P. A. Pilavachi, A. Chletsis, “Economic evaluation of energy saving measures in a common type of Greek building,” Appl. Energy, vol. 86(12), 2550–2559, 2009. https://doi.org/10.1016/J.APENERGY.2009.04. 029
  9. S. Ji, G. Cao, J. Zhang, F. Yu, D. Li, J. Yu, “Lighting design of underground parking with tubular daylighting devices and LEDs,” Opt. – Int. J. Light Electron Opt., 127(3), 1213–1216, 2016. https://doi.org/10.1016/j.ijleo. 2015.10.189
  10.  P. K. Soori S. Alzubaidi, “Study on improving the energy efficiency of office building’s lighting system design” in 2011 IEEE GCC Conference and Exhibition, 2011. https://doi.org/10.1109/IEEEGCC.2011.5752604
  11.  D. Singh, C. Basu, M. Meinhardt-Wollweber, B. Roth, “LEDs for energy efficient greenhouse lighting,” Renew. Sustain. Energy Rev., 49, 139–147, 2015. https://doi.org/10.1016/j.rser.2015.04.117
  12.  Comisión de Normalización Europea, Iluminación de los lugares de trabajo en interiores. Unión Europea, 2002.
  13. Instituto Ecuatoriano de Seguridad Social, Reglamento de Seguridad y salud de los trabajadores y mejoramiento del ambiente de trabajo. Ecuador, 1986.
  14.  T. L. Saaty, “Decision making with the analytic hierarchy process,” Int. J. Serv. Sci., 1(1), 83–98, 2008.
  15.  N. Sapag Chain, R. Sapag Chain, Preparación y evaluación de proyectos, McGraw Hill Interamericana, 2008.
  16.  L. Blank and A. Tarquin, Ingeniería Económica. McGraw-Hill Interamericana, 2006.
  17. Banco Central del Ecuador, Información económica, 2018. Available: https://www.bce.fin.ec/index.php/informacioneconomica.
  18. L. Alboteanu, G. Manolea, “Photovoltaic lighting for an educational room,” in 2013 4th International Symposium on Electrical and Electronics Engineering (ISEEE), Galati, Romania, 2013. https://doi.org/ 10.1109/IEEEGCC.2011.5752604
  19. S. Alzubaidi, P. K. Soori, “Energy Efficient Lighting System Design for Hospitals Diagnostic and Treatment Room—A Case Study,” J. Light Vis. Environ., 36(1), 23–31, 2012. https://doi.org/10.2150/jlve.36.23
  20.  L. E. Mavromatidis, X. Marsault, H. Lequay, “Daylight factor estimation at an early design stage to reduce buildings’ energy consumption due to artificial lighting: A numerical approach based on Doehlert and Box–Behnken designs,” Energy, 65, 488–502, 2014. https://doi.org/ 10.1016/j.energy.2013.12.028
  21.  K. Zalatis, K. Berzina, “Effective and optimal simulation of light design in Riga Technical university’s lighting laboratory from the point of view of energy efficiency,” in 2016 IEEE 4th Workshop on Advances in Information, Electronic and Electrical Engineering (AIEEE), Vilnius, Lithuania, 2016. https://doi.org/10.1109/AIEEE.2016.7821822

Citations by Dimensions

Citations by PlumX

Google Scholar

Scopus